Automation Products
The compact dimensions of the Standard variant of XC1001-A are ideally adapted for single-sector applications, small to medium installations. It provides a full range of monitored inputs and outputs as well as digital and relay outputs. Self-contained control panel including fire detection and extinguishing control. The configurable relay outputs can be used to transmit information to a FS20/FS720 fire detection panel via FDnet/C-NET I/O modules.
The detection lines can be configured to AlgoRex‚ Cerberus PRO‚ Sinteso and Synova conventional and collective devices.
Easy and fast commissioning using 4 digital displays.
Specifications
Mains voltage | AC 115...230 V / +10...-15 %, 50/60 Hz |
Power consumption | 150 VA |
Alarm relay output (NO/NC) | 30 V / 1 A max. |
Battery capacity | 2 x 12 V / 4.5 Ah |
Operating temperature | -5…40 °C |
Conventional line | 3 |
Control output | 24 V / 1 A max. |
Control input | 4 monitored inputs (loss of agent, pressure switch) 4 non monitored inputs (activation via contacts) |
Storage temperature | -20…+60 °C |
Standard | EN 12094-1 , EN 54-2/A1 , EN 54-4/A2 |
Case protection category | IP30 |
Color housing/cover | / Signal white, ~RAL 9003 |
Color | Grey white, RAL 9002 |
Dimensions (W x H x D) | 370 x 286 x 90 mm |
Dimensions (W x H x D) | 370 x 286 x 90 mm |
Weight (net) | 4.1 kg |
Operating altitude, max. | 4000 m |