Automation Products
The FC121-ZA is a conventional fire control panel with an integrated operating unit for 2 zones. The control unit has been designed to be very simple to use while offering exceptional flexibility via a comprehensive feature list. The FC121-ZA is ideally suited for small applications, e.g. in schools, shops, hotels. Expansions and accessories must be ordered separately.
Specifications
Mains voltage | AC 196...253 V |
Operating voltage | DC 21…28.6 V |
Power supply | 25 W |
Operating current | 900 mA |
Bypass time for emergency power supply | 72 h |
Battery capacity | 2x 12 V / 4 or 7 Ah |
Operating temperature | -5…40 °C |
Relay outputs | 1x dialer fault |
Monitored output | 1x sounder line , 1x dialer fire |
Programmable inputs | 2 |
Plug-in position | 1 |
Zones | 2 |
Conventional devices per zone | Max. 32 |
Relative humidity | ≤95 % rel. (no condensation) |
Storage temperature | -20…+60 °C |
Protection category | IP30 |
Color housing/cover | Gray, ~RAL 000 50 00 |
Dimensions (W x H x D) | 310 x 360 x 85 mm |
Dimensions (W x H x D) | 310 x 360 x 85 mm |
Weight (net) | 2.79 kg |