Automation Products
Specification:
Feature | Specification |
Mains Operating Voltage & Power Ranges | 1 AC 200 V to 240 V ± 10 % 0,12 kW – 3,0 kW (0,16 hp – 4,0 hp) 3 AC 200 V to 240 V ± 10 % 0,12 kW – 5,5 kW (0,16 hp – 7,5 hp) 3 AC 380 V to 480 V ± 10 % 0,37 kW – 11,0 kW (0,50 hp – 15,0 hp) |
Input Frequency | 47 Hz to 63 Hz |
Output frequency | 0 Hz to 650 Hz |
Power Factor | ≥ 0,7 |
Inverter Efficiency | 96 % to 97 % |
Overload Capability | 50 % overload capability for 60 s within 5 min period referred to the rated output current |
Operation Temperature | -10 °C to +50 °C (14 °F to 122 °F) |
Storage Temperature | -40 °C to +70 °C (-40 °F to 158 °F) |
Application:
Increase your safety and efficiency with SINAMICS G120C (3 AC 400 V) and SINAMICS G120 (1/3 AC 230 V)
- Safety Integrated functionality
- PROFINET communication
- Perfect integration into automation